Product : ISaGRAF V3
Date : 6-January-1997
File : TICCode.general information and post-processor.htm
Subject : TIC code general information and post-processor
Keywords: TIC - post-processor - SFC engine
____________________________________________________________________
The ISaGRAF code generator can produce either C source code or "TIC"
target independent code. The TIC code is the common point of the
upgrade compatibility between ISaGRAF workbenches and target
systems.
The TIC code is public and fully documented so that any one can use
it as a first specification to design a PLC like or soft logic
target system.
The code produced by ISaGRAF groups, in the same structured file,
the following types of information:
- application configuration
- SFC chart in binary format (lists of steps and transitions)
- instructions in binary TIC code
The SFC chart can be handled by any SFC engine such as a matrix
based state machine. If such a software is not available on the
target, the ISaGRAF workbench is also capable of translating the
SFC charts into natural instructions so that processing the TIC
code is enough to run a complete application containing all 5 IEC
1131-3 languages.
The TIC code is an easy classical 3 address binary code with typed
instructions. As other pieces of information concerning the
application structure are stored with it in the produced code, it
is very easy to build a post processor between the ISaGRAF
workbench and any proprietary target system.
____________________________________________________________________
Copyright © 1996-2009 ICS Triplex ISaGRAF Inc. All rights reserved.